# Power Distribution Hub Specifications

The following tables provide the operating and mechanical specifications for the Power Distribution Hub (PDH).

{% hint style="danger" %}
DO NOT exceed the maximum electrical specifications. Doing so will cause permanent damage to the Power Distribution Hub and will void the warranty.
{% endhint %}

{% hint style="danger" %}
The Power Distribution Hub's reverse polarity protection DOES NOT protect downstream devices. Verify the correct polarity on all power wires before operation.
{% endhint %}

## Main Electrical Specifications

<table><thead><tr><th width="200">Parameter</th><th align="center">Min</th><th width="145" align="center">Typ</th><th align="center">Max</th><th align="center">Units</th></tr></thead><tbody><tr><td>Operating Voltage Range</td><td align="center">4.7</td><td align="center">12</td><td align="center">18</td><td align="center">V</td></tr><tr><td>Power Input Wire Gauge (Bare Solid)</td><td align="center">18</td><td align="center">-</td><td align="center">6</td><td align="center">AWG</td></tr><tr><td>Power Input Wire Gauge (Bare Stranded)</td><td align="center">18</td><td align="center">-</td><td align="center">4</td><td align="center">AWG</td></tr><tr><td>Power Input Bare Wire Strip Length</td><td align="center">0.72</td><td align="center">0.75</td><td align="center">0.79</td><td align="center">in</td></tr><tr><td>Power Input Wire Gauge (Stranded, with ferrule) †</td><td align="center">18</td><td align="center">-</td><td align="center">6</td><td align="center">AWG</td></tr><tr><td>Input Voltage Measurement Resolution</td><td align="center">-</td><td align="center">7.81</td><td align="center">-</td><td align="center">mV</td></tr></tbody></table>

|  †  | If using a ferrule, we recommend using square or hex shaped crimps. |
| :-: | ------------------------------------------------------------------- |

{% hint style="warning" %}
Make sure to consider the current and safety requirements when choosing a wire gauge for any given application.
{% endhint %}

### CAN Specifications

<table><thead><tr><th width="200">Parameter</th><th align="center">Min</th><th width="145" align="center">Typ</th><th align="center">Max</th><th align="center">Units</th></tr></thead><tbody><tr><td>CAN Termination</td><td align="center">-</td><td align="center">120</td><td align="center">-</td><td align="center">Ω</td></tr><tr><td><strong>Latching WAGO Connectors</strong> †</td><td align="center"></td><td align="center"></td><td align="center"></td><td align="center"></td></tr><tr><td>CAN Terminal Wire Gauge (Bare Solid/Stranded)</td><td align="center">26</td><td align="center">-</td><td align="center">14</td><td align="center">AWG</td></tr><tr><td>CAN Terminal Bare Wire Strip Length</td><td align="center">0.31</td><td align="center">0.33</td><td align="center">0.35</td><td align="center">in</td></tr><tr><td>CAN Terminal Wire Gauge (Stranded, with ferrule) ††</td><td align="center">22</td><td align="center">-</td><td align="center">18</td><td align="center">AWG</td></tr><tr><td><strong>Push Button WAGO Connectors</strong> †</td><td align="center"></td><td align="center"></td><td align="center"></td><td align="center"></td></tr><tr><td>CAN Terminal Wire Gauge (Bare Solid/Stranded)</td><td align="center">24</td><td align="center">-</td><td align="center">18</td><td align="center">AWG</td></tr><tr><td>CAN Terminal Bare Wire Strip Length</td><td align="center">0.33</td><td align="center">0.35</td><td align="center">0.37</td><td align="center">in</td></tr><tr><td>CAN Terminal Wire Gauge (Stranded, with ferrule) ††</td><td align="center">28</td><td align="center">-</td><td align="center">20</td><td align="center">AWG</td></tr></tbody></table>

|  †  | As of 01/04/2024, orders made from REV Robotics will ship with the version of the Power Distribution Hub that features Latching WAGO Connectors on the CAN terminal blocks. |
| :-: | --------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
|  †† | If using a ferrule, we recommend using square or hex shaped crimps.                                                                                                         |

### High Current Channel Specifications

<table><thead><tr><th width="207">Parameter</th><th width="158" align="center">Min</th><th align="center">Typ</th><th align="center">Max</th><th align="center">Units</th></tr></thead><tbody><tr><td>Fuse/Circuit Breaker Size</td><td align="center">-</td><td align="center">ATO/ATC</td><td align="center">-</td><td align="center">-</td></tr><tr><td>Supported Fuse/Circuit Breaker Current Rating</td><td align="center">-</td><td align="center">-</td><td align="center">40</td><td align="center">A</td></tr><tr><td>Channel Current Measurement Range</td><td align="center">0</td><td align="center">-</td><td align="center">127.9</td><td align="center">A</td></tr><tr><td>Channel Current Measurement Resolution</td><td align="center">-</td><td align="center">125</td><td align="center">-</td><td align="center">mA</td></tr><tr><td>Supported Wire Gauge (Bare Solid/Stranded)</td><td align="center">24</td><td align="center">-</td><td align="center">8</td><td align="center">AWG</td></tr><tr><td>Bare Wire Strip Length</td><td align="center">0.43</td><td align="center">0.5</td><td align="center">0.51</td><td align="center">in</td></tr><tr><td>Supported Wire Gauge (Stranded, with ferrule) †</td><td align="center">24</td><td align="center">-</td><td align="center">10</td><td align="center">AWG</td></tr></tbody></table>

|  †  | If using a ferrule, we recommend using square or hex shaped crimps. |
| :-: | ------------------------------------------------------------------- |

### Low Current Channel Specifications

<table><thead><tr><th width="228">Parameter</th><th align="center">Min</th><th width="166" align="center">Typ</th><th align="center">Max</th><th align="center">Unit</th></tr></thead><tbody><tr><td>Fuse/Circuit Breaker Size</td><td align="center">-</td><td align="center">ATM/APM</td><td align="center">-</td><td align="center">-</td></tr><tr><td>Continuous Output Current</td><td align="center">-</td><td align="center">-</td><td align="center">15</td><td align="center">A</td></tr><tr><td>Single Channel Peak Output Current †</td><td align="center">-</td><td align="center">-</td><td align="center">20</td><td align="center">A</td></tr><tr><td>Supported Fuse/Circuit Breaker Current Rating</td><td align="center">-</td><td align="center">-</td><td align="center">15</td><td align="center">A</td></tr><tr><td>Supported Fuse/Circuit Breaker Current Rating for PH and PCM (See note below)</td><td align="center">-</td><td align="center">-</td><td align="center">20</td><td align="center">A</td></tr><tr><td>Channel Current Measurement Range </td><td align="center">0</td><td align="center">-</td><td align="center">31.94</td><td align="center">A</td></tr><tr><td>Channel Current Measurement Resolution</td><td align="center">-</td><td align="center">62.5</td><td align="center">-</td><td align="center">mA</td></tr><tr><td><strong>Latching WAGO Connectors</strong> ††</td><td align="center"></td><td align="center"></td><td align="center"></td><td align="center"></td></tr><tr><td>Supported Wire Gauge (Bare Solid/Stranded)</td><td align="center">26</td><td align="center">-</td><td align="center">14</td><td align="center">AWG</td></tr><tr><td>Bare Wire Strip Length</td><td align="center">0.31</td><td align="center">0.33</td><td align="center">0.35</td><td align="center">in</td></tr><tr><td>Supported Wire Gauge (Stranded, with ferrule) ‡</td><td align="center">22</td><td align="center">-</td><td align="center">18</td><td align="center">AWG</td></tr><tr><td><strong>Push Button WAGO Connectors</strong> ††</td><td align="center"></td><td align="center"></td><td align="center"></td><td align="center"></td></tr><tr><td>Supported Wire Gauge (Bare Solid/Stranded)</td><td align="center">24</td><td align="center">-</td><td align="center">18</td><td align="center">AWG</td></tr><tr><td>Bare Wire Strip Length</td><td align="center">0.33</td><td align="center">0.35</td><td align="center">0.37</td><td align="center">in</td></tr><tr><td>Supported Wire Gauge (Stranded, with ferrule) ‡</td><td align="center">28</td><td align="center">-</td><td align="center">20</td><td align="center">AWG</td></tr></tbody></table>

{% hint style="info" %}
It is recommended to use a 20A fuse for a single Pneumatic Hub or Pneumatic Control Module connected to any of the three Low-current Channels if using a compressor with a higher peak current draw, such as the CP26 or the Thomas 405ADC38.
{% endhint %}

|  †  | Peak current can be sustained for 5 min.                                                                                                                                                  |
| :-: | ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
|  †† | As of 01/04/2024, orders made from REV Robotics will ship with the version of the Power Distribution Hub that features Latching WAGO Connectors on the Low Current Channel's WAGO blocks. |
|  ‡  | If using a ferrule, we recommend using square or hex shaped crimps.                                                                                                                       |

### Switched Channel Specifications

<table><thead><tr><th width="235">Parameter</th><th align="center">Min</th><th width="162" align="center">Typ</th><th align="center">Max</th><th align="center">Unit</th></tr></thead><tbody><tr><td>Continuous Output Current †</td><td align="center">-</td><td align="center">-</td><td align="center">15</td><td align="center">A</td></tr><tr><td>Fuse/Circuit Breaker Size</td><td align="center">-</td><td align="center">ATM/APM</td><td align="center">-</td><td align="center">-</td></tr><tr><td>Supported Fuse/Circuit Breaker Current Rating †</td><td align="center">-</td><td align="center">-</td><td align="center">15</td><td align="center">A</td></tr><tr><td>Low Current Channels </td><td align="center">0</td><td align="center">-</td><td align="center">31.94</td><td align="center">A</td></tr><tr><td>Low Current Channel Resolution </td><td align="center">-</td><td align="center">62.5</td><td align="center">-</td><td align="center">mA</td></tr><tr><td>Switching Frequency </td><td align="center">-</td><td align="center">-</td><td align="center">10</td><td align="center">Hz</td></tr><tr><td><strong>Latching WAGO Connectors</strong> ††</td><td align="center"></td><td align="center"></td><td align="center"></td><td align="center"></td></tr><tr><td>Supported Wire Gauge (Bare Solid/Stranded)</td><td align="center">26</td><td align="center">-</td><td align="center">14</td><td align="center">AWG</td></tr><tr><td>Bare Wire Strip Length</td><td align="center">0.31</td><td align="center">0.33</td><td align="center">0.35</td><td align="center">in</td></tr><tr><td>Supported Wire Gauge (Stranded, with ferrule) ‡</td><td align="center">22</td><td align="center">-</td><td align="center">18</td><td align="center">AWG</td></tr><tr><td><strong>Push Button WAGO Connectors</strong> ††</td><td align="center"></td><td align="center"></td><td align="center"></td><td align="center"></td></tr><tr><td>Supported Wire Gauge (Bare Solid/Stranded)</td><td align="center">24</td><td align="center">-</td><td align="center">18</td><td align="center">AWG</td></tr><tr><td>Bare Wire Strip Length</td><td align="center">0.33</td><td align="center">0.35</td><td align="center">0.37</td><td align="center">in</td></tr><tr><td>Supported Wire Gauge (Stranded, with ferrule) ‡</td><td align="center">28</td><td align="center">-</td><td align="center">20</td><td align="center">AWG</td></tr></tbody></table>

|  †  | Continuous current is thermally limited, therefore it depends on environmental and loading factors. Channel may shut itself off automatically if thermal limits are reached               |
| :-: | ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
|  †† | As of 01/04/2024, orders made from REV Robotics will ship with the version of the Power Distribution Hub that features Latching WAGO Connectors on the Low Current Channel's WAGO blocks. |
|  ‡  | If using a ferrule, we recommend using square or hex shaped crimps.                                                                                                                       |

#### Power Distribution Hub Circuit Breakers

{% hint style="info" %}
[Information about the REV ATO Auto-resetting Circuit Breakers has moved to its own page!](/ion-control/pdh/specs/rev-ato-auto-resetting-breakers.md)
{% endhint %}

## Mechanical Specifications

<table><thead><tr><th width="188">Parameter</th><th align="center">Min</th><th width="155" align="center">Typ</th><th align="center">Max</th><th align="center">Units</th></tr></thead><tbody><tr><td>Body Length</td><td align="center">-</td><td align="center">8.875</td><td align="center">-</td><td align="center">in</td></tr><tr><td>Body Width</td><td align="center">-</td><td align="center">4.375</td><td align="center">-</td><td align="center">in</td></tr><tr><td>Body Height</td><td align="center">-</td><td align="center">1.563</td><td align="center">-</td><td align="center">in</td></tr><tr><td>Weight</td><td align="center">-</td><td align="center">1.14</td><td align="center">-</td><td align="center">lbs</td></tr><tr><td>Mounting Hole Grid Pitch</td><td align="center">-</td><td align="center">0.5</td><td align="center">-</td><td align="center">in</td></tr><tr><td>Mounting Screw Size (Clearance)</td><td align="center">-</td><td align="center">#10</td><td align="center">-</td><td align="center">-</td></tr><tr><td>Case Material</td><td align="center">-</td><td align="center">ABS</td><td align="center">-</td><td align="center">-</td></tr></tbody></table>

{% hint style="danger" %}
DO NOT use thread-locking fluid on the mounting hardware for the REV Power Distribution Hub. Thread-locking fluid will damage the ABS plastic case.
{% endhint %}

### Mechanical Drawings

<figure><img src="/files/G8MHzRJCYWdSrbu7obN5" alt=""><figcaption><p>Power Distribution Hub mechanical drawings top &#x26; front view</p></figcaption></figure>


---

# Agent Instructions: Querying This Documentation

If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter:

```
GET https://docs.revrobotics.com/ion-control/pdh/specs.md?ask=<question>
```

The question should be specific, self-contained, and written in natural language.
The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.