Wiring the Power Distribution Hub

Power Distribution Hub Wiring Diagram

Always make sure the the Power Distribution Hub is disconnected from any power source before adding or modifying connections.

Latching WAGO Terminals: Battery Input and High-Current Channels

  • For Battery Input use 18 to 4 AWG Wire, Stripped back ~0.75” (20mm)

  • For High-Current Channels use 24 to 8 AWG Wire, Stripped back ~0.5” (12mm)

  • Flip open the lever with an upward motion.

    • You can open the lever all the way to have it stay open or you can open it half way for quick wire changes.

  • Insert stripped wire into connector opening.

  • Push down the lever.

  • Test the wire by giving it a smart tug to ensure wire is connected securely.

  • Visually inspect to make sure no stray wires are outside of the connector port.

  • Use 24 to 18 AWG Wire, Stripped back ~0.35” (8mm)

  • Press and hold down connector button.

  • Insert stripped wire into connector opening.

  • Release connector button.

  • Carefully insert the Circuit Breaker (CB) directly into the circuit breaker holder. Ensure that the blades of the circuit breaker slide into the circuit breaker holder.

  • Circuit breakers should not be loose or move at all when inserted correctly.

    • If the circuit breaker is loose, remove the circuit breaker and make sure you can see the opening on the circuit breaker holder, then reinsert into the holder.

  • When removing a circuit breaker, make sure to rock the circuit breaker back and forth to make it easier to pull up on.

Getting Started with the Power Distribution Hub

Welcome to your new Power Distribution Hub from REV Robotics! This documentation is intended to answer any questions related to the Power Distribution Hub (PDH) used in the FIRST Robotics Competition. If there is a question that is not answered by this space, send our support team an email at support@revrobotics.com. We are happy to help point you in the right direction!

  • Have a specific question? Feel free to head straight to it using the navigation bar to the left. Each section is grouped with other similar topics.

  • Have trouble finding what you are looking for? Try the search bar in the upper right!

Install the before continuing with this guide. The REV Hardware Client is the best way to verify that the Power Distribution Hub is configured correctly and is

Test the wire by giving it a smart tug to ensure wire is connected securely.

  • Visually inspect to make sure no stray wires are outside of the connector port.

  • New circuit breaker holders fit circuit breakers tightly. This can make it hard to pull out the circuit breaker.

    Smart Tug - tugging on a wire to test the connection with a reasonable amount of force.

    Push-Button WAGO Terminals: CAN and Low-Current Channels

    Circuit Breakers

    Over time circuit breaker holders will become easier to use and stay snug!

    required
    for using the CAN Interface.

    We recommend reading through this guide in its entirety at least once to fully understand all of the features of your Power Distribution Hub.

    Before You Start

    REV Hardware Client

    RS485 Ports are not currently used in FRC and are included for potential future use