The following tables provide the operating and mechanical specifications for the Power Distribution Hub (PDH).
DO NOT exceed the maximum electrical specifications. Doing so will cause permanent damage to the Power Distribution Hub and will void the warranty.
The Power Distribution Hub's reverse polarity protection DOES NOT protect downstream devices. Verify the correct polarity on all power wires before operation.
Make sure to take into consideration current requirements when choosing wire gauge for any given application.
It is recommended to use a 20A fuse for a single Pneumatic Hub or Pneumatic Control Module connected to any of the three Low-current Channels if using a compressor with higher peak current draw, such as the CP26 or the Thomas 405ADC38.
DO NOT use thread-locking fluid on the mounting hardware for the REV Power Distribution Hub. Thread-locking fluid will damage the ABS plastic case.
Parameter
Min
Typ
Max
Units
Operating Voltage Range
4.7
12
18
V
Power Input Wire Gauge (Bare Solid)
18
-
6
AWG
Power Input Wire Gauge (Bare Stranded)
18
-
4
AWG
Power Input Bare Wire Strip Length
0.72
0.75
0.79
in
Power Input Wire Gauge (Stranded, with ferrule)
18
-
6
AWG
Input Voltage Measurement Resolution
-
7.81
-
mV
CAN Termination
-
120
-
Ω
CAN Terminal Wire Gauge (Bare Solid/Stranded)
24
-
18
AWG
CAN Terminal Bare Wire Strip Length
0.33
0.35
0.37
in
CAN Terminal Wire Gauge (Stranded, with ferrule)
24
-
18
AWG
Parameter
Min
Typ
Max
Units
Fuse/Circuit Breaker Size
-
ATO/ATC
-
-
Supported Fuse/Circuit Breaker Current Rating
-
-
40
A
Channel Current Measurement Range
0
-
127.9
A
Channel Current Measurement Resolution
-
125
-
mA
Supported Wire Gauge (Bare Solid/Stranded)
24
-
8
AWG
Bare Wire Strip Length
0.43
0.5
0.51
in
Supported Wire Gauge (Stranded, with ferrule)
23
-
10
AWG
Parameter
Min
Typ
Max
Unit
Fuse/Circuit Breaker Size
-
ATM/APM
-
-
Continuous Output Current
-
-
15
A
Single Channel Peak Output Current †
-
-
20
A
Supported Fuse/Circuit Breaker Current Rating
-
-
15
A
Supported Fuse/Circuit Breaker Current Rating for PH and PCM (See note below)
-
-
20
A
Channel Current Measurement Range
0
-
31.94
A
Channel Current Measurement Resolution
-
62.5
-
mA
Supported Wire Gauge (Bare Solid/Stranded)
24
-
18
AWG
Bare Wire Strip Length
0.33
0.35
0.37
in
Supported Wire Gauge (Stranded, with ferrule)
23
-
18
AWG
†
Peak current can be sustained for 5 min.
Parameter
Min
Typ
Max
Unit
Continuous Output Current †
-
-
15
A
Fuse/Circuit Breaker Size
-
ATM/APM
-
-
Supported Fuse/Circuit Breaker Current Rating †
-
-
15
A
Low Current Channels
0
-
31.94
A
Low Current Channel Resolution
-
62.5
-
mA
Switching Frequency
-
-
10
Hz
Supported Wire Gauge (Bare Solid/Stranded)
24
-
18
AWG
Bare Wire Strip Length
0.33
0.35
0.37
in
Supported Wire Gauge (Stranded, with ferrule)
23
-
18
AWG
†
Continuous current is thermally limited, therefore it depends on environmental and loading factors. Channel may shut itself off automatically if thermal limits are reached
Parameter
Min
Typ
Max
Units
Body Length
-
8.875
-
in
Body Width
-
4.375
-
in
Body Height
-
1.563
-
in
Weight
-
1.14
-
lbs
Mounting Hole Grid Pitch
-
0.5
-
in
Mounting Screw Size (Clearance)
-
#10
-
-
Case Material
-
ABS
-
-